Voltage Drop Calculator - NEC Compliant Wire Sizing Tool

Calculate the voltage drop across any cable run and instantly check against NEC 3% and 5% recommended limits. Works for AC and DC circuits with copper or aluminum conductors.

Data Privacy & Security

100% Local Processing. All calculations run entirely in your browser. No data is transmitted to external servers.

Circuit Parameters

Voltage Drop
—
Volts lost across the cable run
Percentage Drop
—
0%3% NEC Branch5% NEC Max
Voltage at Load End
—
Actual voltage received by the load
Enter values above to check NEC compliance.
Live Cable Run Diagram
SOURCE 120 V 12 AWG Copper — 100 ft one-way LOAD — V ▼ — V drop (—%)

How to Use the Voltage Drop Calculator

  1. Select your conductor material (Copper or Aluminum) and wire gauge (AWG).
  2. Enter the one-way cable run length in feet or meters.
  3. Enter the load current in Amperes and the source voltage.
  4. The calculator displays the voltage drop, percentage drop, and NEC compliance status in real time.

NEC Voltage Drop Guidelines

≤ 3%
NEC Branch Circuit Limit
Recommended maximum for branch circuit runs (NEC 210.19 informational note)
≤ 5%
NEC Total System Limit
Maximum total drop from service panel to final load (NEC 215.2 informational note)

Frequently Asked Questions

What is an acceptable voltage drop percentage?

The NEC recommends a maximum 3% voltage drop for branch circuits and 5% total from service panel to the final load. Most electricians aim to keep branch circuit drop under 3% for optimal performance and energy efficiency.

How is voltage drop calculated?

Voltage drop is calculated using: V_drop = 2 × L × R_per_ft × I, where L is the one-way cable length in feet, R_per_ft is the resistance per foot of the wire (from conductor tables), and I is the current in amperes. The factor of 2 accounts for both the outgoing and return conductors.

Is copper or aluminum wire better for long cable runs?

Copper wire has lower resistivity (~1.72 μΩ·cm) compared to aluminum (~2.82 μΩ·cm), meaning copper produces significantly less voltage drop for the same gauge and length. Aluminum is lighter and cheaper, and is commonly used in utility and large feeder applications.

How do I reduce voltage drop?

To reduce voltage drop: (1) Use a larger wire gauge (lower AWG number), (2) Shorten the cable run, (3) Increase the supply voltage, or (4) Reduce the load current. Increasing wire gauge by 3 AWG sizes (e.g., 12 AWG to 9 AWG) approximately halves the resistance.

What is the voltage drop formula for 12V DC systems?

For 12V DC systems, voltage drop is especially critical because 3% equals only 0.36V. The formula is the same: V_drop = 2 × L × R × I. Because the source voltage is low, even a small drop becomes a large percentage. This calculator automatically handles 12V, 24V, 48V, and any other voltage you enter.

What is the NEC voltage drop recommendation?

NEC Article 210.19 (informational note) recommends a maximum 3% voltage drop on branch circuits. NEC 215.2 recommends 5% maximum total voltage drop from the service panel to the final load. These are recommendations, not hard requirements, but they represent best practice for safe and efficient installations.

Does wire temperature affect voltage drop?

Yes. As wire temperature increases, resistance increases. The resistance values used in this calculator are at 20°C (68°F) standard conditions. At higher operating temperatures (e.g., 75°C conductor temperature), actual resistance and voltage drop will be higher — typically by 15–25% for copper at full rated temperature.

What causes voltage drop in a circuit?

Voltage drop is caused by the inherent electrical resistance of conductors. Every wire has resistance based on its material, length, and cross-sectional area. As current flows through this resistance, some energy is converted to heat (following P = I²R), resulting in a lower voltage at the load end of the circuit.

Limitations

This calculator assumes standard conductor temperature at 20°C and does not account for conduit fill factors, ambient temperature corrections, or bundling derating per NEC 310.15. For code-compliant electrical designs, always consult a licensed electrician or engineer.

Data Privacy & Security

This Voltage Drop Calculator runs entirely in your web browser. No circuit parameters or electrical specifications are sent to any external server, ensuring complete privacy for your electrical engineering projects.

Related Tools